Spot network substation : ウィキペディア英語版
Spot network substation
In electricity distribution networks, spot network substations are used in interconnected distribution networks. They have the secondary network (also called a grid network) with all supply transformers bussed together on the secondary side at one location. Spot networks are considered the most reliable and most flexible arrangement of connecting power to all types of loads.〔(Cugnet, Pierre: Master's Thesis - Power Distribution Systems )〕 Switching can be done without interrupting the power to the loads.
==Description==
Electricity distribution networks are typically of two types, radial or interconnected. A radial network arranges the station and branches like a tree with no connection to any other supply. This is typical of long rural lines with isolated load areas. In general, the radial distribution network has more power failures than the interconnected distribution networks.
In a secondary network the transformers are distributed across an area (e.g. in streets) and have multiple supplies. The transformers are wired together on the secondary side. The system is arranged so that nearby transformers do not use the same feeder. In case of an issue with a feeder (or transformer) the load is fed by nearby transformers, so there is no interruption, perhaps some voltage drop. Usually a fault on the secondary side is not a big problem since the conductors will destroy themselves.
A spot network is basically a secondary network condensed to a point. Several transformers have multiple supplies and their secondaries are bussed together. Besides a region-wide blackout, they are vulnerable to a bus fault, which is extremely rare. The simplest case is where each transformer connects to one feeder and vice versa ("unit system"). High-voltage switching can be used to handle more cases, e.g., working transformer but faulty feeder or the reverse.
Urban (spot) network substations can be used to make interconnected distribution networks to serve a single facility. Examples of such single facilities include airports, hospitals, major data processing centers (especially those using uninterruptible power supply), and sports arenas that regularly broadcast nationally televised events.
In large cities, many electric utility companies use grid feeders to make interconnected distribution networks to serve the downtown core. The interconnected network has multiple connections to the points of supply.
Network protectors, (reverse current relays), are used to detect any open circuits that are letting the electrical current flow back towards its source.